LQ: Arcadia + LQ-4WG2 <> 2-Way Radio
Running firmware – Arcadia R4.1 & LQ v5.3.18
I.V.Directs Setup:
Arcadia CCM > Hardware > Resources > I.V.Directs > Click + to add new > Select LQ Signaling > Create.
Set up Credentials for LQ to authenticate and establish link.
More info: Arcadia : How to connect LQ to Arcadia with I.V.Direct?
On LQ CCM > Accounts > IVD > Click + to add new.
Ensure IP/Hostname is set to Arcadia’s Management IP address and is reachable.
Port is default 6002.
Port Settings > Click + > Enter User ID and Password (as set on Arcadia) > Select LQ Device to use this port on and with.
Assignments and Port Settings
Arcadia CCM > Configuration > Channels > Select Channel to use IVD Port with
From the Ports list on the right > scroll down and click + on created IVD Port to assign it to Channel.
LQ CCM > Assignments > Select Channel > Assignment IVD Port + LQ’s 4WG2 Port to Channel.
LQ CCM > Device > Ports > Select IVD Port > Adjust VOX Settings (this is to use VOX to trigger GPO; detects audio signal arriving into port)
Settings below are a good starting point if VOX is used
Now adjust the 4-Wire + GPIO Port Settings.
Note that Output Level can be adjusted either to 0dB (Line Level) or -55dB (Mic Level)
These settings allows VOX (someone speaking into channel) to trigger Control Event 1 which triggers GPO.
Other options include Call Control Event or a Call (as LQ Signaling is enabled between Arcadia & LQ) signal to trigger GPO based on needs.
VOX may not always be the preferred solution; consider operating environment.