IP CON: what is the delay between a LQ GPI on and active GPO

IP CON: what is the delay between a LQ GPI on and active GPO

Here are the test results for the LQ GPI -> GPO delay (latency): testedon a local switch and not taking into account any long network latency
- 60 ms between 2 LQ in a link group (± 8ms)
- 57 ms between 2 ports in one LQ (± 8ms)
- no variation regarding GPO from 0->1 versus 1->0 (means the samelatency happens for GPIO rising vs. falling)
- the test equipment needed for these measurements also allowed the "GPOoff delay" to be tested precisely as well. Result: Accuracy is good (butthe user must also add the inherent 60 ms latency to any GPO delay setting aswell as any network )
Q:At what point do GPOs start getting dropped (when GPIs come in too fast)?
Result: If GPIs are spaced 310 ms or more, the GPOs don't get dropped/lost.This means the rate of GPOs is the same as for GPIs except if they are spacedless than 310 ms apart. The smaller the spacing, the more GPOs are dropped.


Related content

CAN'T FIND YOUR ANSWER? CLICK HERE TO CONTACT SUPPORT


This solution was provided by Clear-Com via a question submitted to us by customers like you. If you wish to share with us a new solution or update an old one, please follow this link..


The information on this page is owned by Clear-Com and constitutes Clear-Com’s confidential and proprietary information, may be used solely for purposes related to the furtherance of Clear-Com’ business and shall not be disclosed, distributed, copied or disseminated without Clear-Com’s prior written consent. Click Here for Clear-Com's privacy statement.