Question: How do we link Sonifex model: LD-20F1ONA ON-AIR Light with Clear-Com V-series Panel to change the light from green to red?
Answer: Here are the steps: 1) Wired up the aux relay to toggle switch with reference from manualsection 4-11(page 2). Pin 3, 15 and 16. a) Green light atN/C: Pin 3 & 15b) Red light atN/O: Pin 3 & 16. 2) Go to ECS > Configuration > Controls: Create a controlin ECS (see attached Panel GPO Control.pdf). attach the Panel Aux relay to the control 3) Configuration > Panels: Add Control label to any panel (seeattached Panel programming GPO) Important notes:Relays are rated at 1 Amp at 24 VDC. This relay is not designed forswitching mains AC line voltage. To switchan external device running on mains AC line voltage, use an externalrelay (or other switching mechanism) activated by this relay.
Diagram for Sonifex LD-20F1ONA ON-AIR Light with Clear-Com V-series Panel: OnAir_Relay Sonifex LD 20F1ONA.pdf
Answer: Here are the steps: 1) Wired up the aux relay to toggle switch with reference from manualsection 4-11(page 2). Pin 3, 15 and 16. a) Green light atN/C: Pin 3 & 15b) Red light atN/O: Pin 3 & 16. 2) Go to ECS > Configuration > Controls: Create a controlin ECS (see attached Panel GPO Control.pdf). attach the Panel Aux relay to the control 3) Configuration > Panels: Add Control label to any panel (seeattached Panel programming GPO) Important notes:Relays are rated at 1 Amp at 24 VDC. This relay is not designed forswitching mains AC line voltage. To switchan external device running on mains AC line voltage, use an externalrelay (or other switching mechanism) activated by this relay.
Diagram for Sonifex LD-20F1ONA ON-AIR Light with Clear-Com V-series Panel: OnAir_Relay Sonifex LD 20F1ONA.pdf
, multiple selections available,
Related content
Matrix: How can I program the 2 relays on the V series panels
Matrix: How can I program the 2 relays on the V series panels
More like this
Matrix: How do I wire up the V-Panel logic inputs to a panel switch or foot switch?
Matrix: How do I wire up the V-Panel logic inputs to a panel switch or foot switch?
More like this
Matrix: How can I trigger a V-Panel Aux relay from another panel?
Matrix: How can I trigger a V-Panel Aux relay from another panel?
More like this
Matrix: How do I program the V series panel GPI 1 and 2 (logic) inputs
Matrix: How do I program the V series panel GPI 1 and 2 (logic) inputs
More like this
Matrix: Can we get a button on a panel to blink whenever there is audio present on a 4wire port
Matrix: Can we get a button on a panel to blink whenever there is audio present on a 4wire port
More like this
Matrix: I-Station Configuration For AUX-101 GPI's on Eclipse
Matrix: I-Station Configuration For AUX-101 GPI's on Eclipse
More like this
CAN'T FIND YOUR ANSWER? CLICK HERE TO CONTACT SUPPORT
This solution was provided by Clear-Com via a question submitted to us by customers like you. If you wish to share with us a new solution or update an old one, please follow this link..
The information on this page is owned by Clear-Com and constitutes Clear-Com’s confidential and proprietary information, may be used solely for purposes related to the furtherance of Clear-Com’ business and shall not be disclosed, distributed, copied or disseminated without Clear-Com’s prior written consent. Click Here for Clear-Com's privacy statement.